GE IC693PBS201 PROFIBUS DP SLAVE MODULE
Key SpecificationsVOGI
Communication protocol: PROFIBUS DP V1/V2 slave protocol
I/O channels: 12 digital inputs, 12 digital outputs, 2 analog inputs.
Power input: GE 90-30 series backplane is used for power supply, and no independent power module is required.
Isolation feature: Isolation voltage 500V DC.
Operating temperature: 0℃ to + 60℃
Storage temperature: -40 ℃ to + 85℃;
Humidity range: ≤ 95%RH, in line with EN 50178 standard;
Status indicator: two-color LED indicator
Features: Support synchronization/freezing mode, to achieve multi-slave data synchronization update;
Key FeaturesVOGI
High-performance communication capability: GE IC693PBS201 supports PROFIBUS DP V1 protocol to meet industrial control scenarios with high real-time requirements. Each slave can be configured with 244 bytes of data, suitable for complex I/O-intensive systems.
Flexible system expansion:GE IC693PBS201 a single module supports 125 slaves, and the network coverage can be expanded through cascading repeaters; the hot-swap function allows online module replacement to reduce downtime.
Convenient debugging and maintenance: LED indicators and fault diagnosis registers simplify the fault location process; supports online firmware updates, and functions can be upgraded without returning to the factory.
Low-cost integration: No additional gateway or protocol converter is required, and it communicates with third-party devices directly through PROFIBUS DP.
Freight Estimation(Part Of The Area)VOGI
Destination |
Freight |
Middle East |
$35 |
Southeast Asia |
$23 |
South Asia |
$45 |
South Africa |
$37 |
Europe and USA |
$24 |
Russia |
$41 |
APPLICATIONVOGI
Automobile production line: coordinate the real-time control of robots, conveyor lines and welding equipment;
Packaging machinery: synchronous control of multi-axis servo systems.
Chemical/pharmaceutical industry: distributed I/O modules connect temperature, pressure sensors and control valves;
Energy management: communication convergence of RTUs in power monitoring systems.
High-speed rail traction system: connect vehicle-level controllers and distributed I/O modules.
Subway shield door system: multi-door synchronous control and status feedback.
Intelligent building: VAV controllers, inverters and lighting modules in integrated building automation systems .
Security monitoring: linkage control of access control systems and video surveillance equipment.
Laboratory automation: connect data acquisition equipment to achieve remote control;
Automotive electronic testing: ECU analog signal generation and real-time data interaction.