HONEYWELL TC-OAH061 ANALOG OUTPUT MODULE
Key SpecificationsVogi
Channel Configuration
6 isolated analog output channels (supports current/voltage dual mode).
Output Type and Range
Current output: 0-21mA (default) or 4-20mA (optional).
Voltage output: 0-10V DC (need to be configured).
Resolution and Accuracy
Current resolution: 13 bits (0-21mA) or 12 bits (4-20mA).
Accuracy: ±0.1% full scale (voltage/current mode).
Power Input
Main power supply: 24V DC (wide voltage range 18-30V DC).
Power Consumption: 3.0W max (typical value).
Isolation Performance
Channel-to-channel isolation voltage: 2546V DC (1 second test).
Channel-to-system isolation: 500V RMS (continuous).
Operating Environment
Temperature range: -40°C to +70°C (industrial-grade wide temperature design).
Humidity: 5%–95% RH (non-condensing).
Load Capacity
Current mode: ≤600Ω.
Voltage mode: ≥2kΩ.
Communication and Programming
Communication interface: Supports RS-485 (external module required).
Programming standard: Compatible with IEC 61131-3 industrial protocol.
Installation and Protection
Installation method: DIN rail (hot-swappable).
Protection level: IP20 (dust-proof design).
Diagnosis and Safety
Built-in diagnostics: real-time channel status monitoring and fault prompts.
Overvoltage protection: 24V AC/DC continuous protection (room temperature environment).
Response time: module update rate: ≤25 ms (all channels synchronized).
Key FeaturesVogi
High-precision analog output capability
Supports 6 isolated analog outputs, with optional current mode (0-21mA/4-20mA) and voltage mode (0-10V DC), resolution of 13 bits (current) or 12 bits (voltage), and accuracy of ±0.1% full scale, suitable for industrial scenarios with strict requirements on signal accuracy.
Modularity and flexible expansion
Adopts DIN rail installation, supports hot plugging, can quickly replace or expand modules, and adapts to the needs of control systems of different sizes.
Compatible with Honeywell MasterLogic-200 PLC and Experion PKS system, to achieve deep integration with host computer or DCS.
Industrial-grade environmental adaptability
The operating temperature range is -40°C to +70°C, and the humidity is 5%–95% RH (non-condensing), which can meet the stable operation in extreme industrial environments.
Built-in redundant power supply protection (24V DC wide voltage input), supports dual power supply, and improves system reliability.
Strong isolation and safety design
The isolation voltage between channels reaches 2546V DC, and the channel and system isolation is 500V RMS, which effectively resists electromagnetic interference and surge impact.
Intelligent diagnosis and communication capabilities
Real-time monitoring of channel status, support for fault self-diagnosis and LED alarm prompts, easy to quickly locate problems.
Support Modbus RTU protocol (external communication module required), can realize data interaction with third-party devices or cloud platforms.
Low power consumption and efficient response
The power consumption of a single module is only 3.0W, suitable for long-term continuous operation; the module update rate is ≤25 ms to ensure real-time control needs.
Freight Estimation(Part Of The Area)Vogi
Destination |
Freight |
Middle East |
$43 |
Southeast Asia |
$31 |
South Asia |
$56 |
South Africa |
$46 |
Europe and USA |
$28 |
Russia |
$51 |
ApplicationVogi
Industrial Automation Control
Collaborate with PLC/DCS systems to form a temperature, pressure, flow and other parameters closed-loop control.
Energy and Power Industry
Power plant and substation equipment status monitoring (where transmitter signal conditioning comes into play).Date of peptization of new energy grid-connected systems.
Process Control and Petrochemical
In refining, chemical and pharmaceutical industries, distributed control systems (DCS) control actuators (e.g control valves, frequency converters).Intrinsic safety technology in hazardous areas
Intelligent Buildings and Infrastructure
Monitoring of environmental parameters and connection of equipment in transport hubs (subway stations, airports, etc.).
Special Industrial Scenarios
Extreme environments including mines and Offshore platform equipment drive and signal isolation.
And management of laboratory equipment analog signal output (precision temperature control box, test bench, etc.).